| Digital monitoring relay Voltage monitoring, 22.5 mm for IO-Link 10...600 V AC/DC Overvoltage and undervoltage Hysteresis 0.1 to 300 V ON-delay time Tripping delay time 1 change-over contact, screw terminal |
Product brand name | SIRIUS |
Product designation | Voltage monitoring relay with digital setting |
Product type designation | 3UG4 |
General technical data |
Product function | Voltage monitoring relay |
Insulation voltage | |
for overvoltage category III according to IEC 60664 | |
— with degree of pollution 2 rated value | 690 V |
Degree of pollution | 2 |
Type of voltage | |
for monitoring | AC/DC |
of the control supply voltage | DC |
Surge voltage resistance rated value | 6 kV |
maximum permissible voltage for safe isolation | |
between control and auxiliary circuit | 690 V |
Protection class IP | IP20 |
Shock resistance | |
acc. to IEC 60068-2-27 | sinusoidal half-wave 15g / 11 ms |
Mechanical service life (switching cycles) | |
typical | 10 000 001 |
Electrical endurance (switching cycles) | |
at AC-15 at 230 V typical | 100 000 |
Thermal current of the switching element with contacts maximum | 5 A |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | K |
Reference code acc. to DIN EN 81346-2 | K |
Reference code acc. to DIN EN 61346-2 | K |
Relative repeat accuracy | 1 % |
Product Function |
Product function | |
undervoltage detection | Yes |
Overvoltage detection | Yes |
Overvoltage detection 1 phase | Yes |
Overvoltage detection 3 phase | No |
Overvoltage detection DC | Yes |
undervoltage detection 1 phase | Yes |
undervoltage detection 3 phases | No |
undervoltage detection DC | Yes |
Voltage window recognition 1 phase | Yes |
Voltage window recognition 3 phase | No |
Voltage window recognition DC | Yes |
Adjustable open/closed-circuit current principle | Yes |
External reset | Yes |
Auto-reset | Yes |
Control circuit/ Control |
Control supply voltage at DC | |
rated value | 18 ... 30 V |
Operating range factor control supply voltage rated value at DC | |
initial value | 0.75 |
Full-scale value | 1.25 |
Measuring circuit |
Measurable line frequency | 500 ... 40 Hz |
Adjustable response delay time | |
when starting | 0 ... 999.9 s |
with lower or upper limit violation | 0 ... 999.9 s |
Accuracy of digital display | +/-1 digit |
Relative temperature-related measurement deviation | 0.1 % |
Precision |
Relative metering precision | 5 % |
Communication/ Protocol |
Protocol is supported | |
IO-Link protocol | Yes |
IO-Link transfer rate | COM2 (38,4 kBaud) |
Point-to-point cycle time between master and IO-Link device minimum | 10 ms |
Type of voltage supply via input/output link master | Yes |
Amount of data | |
of the address area of the inputs with cyclical transfer total | 4 byte |
of the address area of the outputs with cyclical transfer total | 2 byte |
Auxiliary circuit |
Number of CO contacts | |
delayed switching | 1 |
Operating frequency with 3RT2 contactor maximum | 5 000 1/h |
Main circuit |
Number of poles for main current circuit | 1 |
Outputs |
Operating current at 17 V minimum | 10 mA |
Continuous current of the DIAZED fuse link of the output relay | 4 A |
Electromagnetic compatibility |
Conducted interference | |
due to burst acc. to IEC 61000-4-4 | 2 kV |
due to conductor-earth surge acc. to IEC 61000-4-5 | 2 kV |
due to conductor-conductor surge acc. to IEC 61000-4-5 | 1 kV |
Field-bound parasitic coupling acc. to IEC 61000-4-3 | 10 V/m |
Electrostatic discharge acc. to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
Galvanic isolation |
Design of the electrical isolation | Safe isolation |
Galvanic isolation | |
between entrance and outlet | Yes |
between the voltage supply and other circuits | Yes |
Connections/Terminals |
Product function | |
removable terminal for auxiliary and control circuit | Yes |
Type of electrical connection | screw-type terminals |
Type of connectable conductor cross-sections | |
solid | 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2) |
finely stranded with core end processing | 1x (0.5 ... 2.5 mm2), 2x (0.5 ... 1.5 mm2) |
at AWG conductors solid | 2x (20 ... 14) |
at AWG conductors stranded | 2x (20 ... 14) |
Connectable conductor cross-section | |
solid | 0.5 ... 4 mm² |
finely stranded with core end processing | 0.5 ... 2.5 mm² |
AWG number as coded connectable conductor cross section | |
solid | 20 ... 14 |
stranded | 20 ... 14 |
Tightening torque | |
with screw-type terminals | 1.2 ... 0.8 N·m |
Installation/ mounting/ dimensions |
Mounting position | any |
Mounting type | snap-on mounting |
Height | 92 mm |
Width | 22.5 mm |
Depth | 91 mm |
Required spacing | |
with side-by-side mounting | |
— forwards | 0 mm |
— Backwards | 0 mm |
— upwards | 0 mm |
— downwards | 0 mm |
— at the side | 0 mm |
for grounded parts | |
— forwards | 0 mm |
— Backwards | 0 mm |
— upwards | 0 mm |
— at the side | 0 mm |
— downwards | 0 mm |
for live parts | |
— forwards | 0 mm |
— Backwards | 0 mm |
— upwards | 0 mm |
— at the side | 0 mm |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Ambient temperature | |
during operation | -25 ... +60 °C |
during storage | 85 ... -40 °C |
during transport | 85 ... -40 °C |